test that be carried out under the following conditions: meter in operating condition, voltage and auxiliary circuits energised with reference voltage ±5 %, without any current in the current circuits and the current terminals shall be open circuit, cable length between surge generator and meter 1 m, tested in differential mode (line to line), phase angle pulses to be applied at 600 and 2400 relative to zero crossing of a.c-supply, test voltage on the current and voltage circuits 4 kV, generator source impedance 2 Ω, test voltage on auxiliary circuits with a reference voltage over 40 V to 1 kV, generator source impedance 42 Ω, number of pulses 5 positive and 5 negative, repetition rate maximum 1/min, test/katse, mis tuleb lävi viia alljärgnevatel tingimustel: tööolukorras arvesti, pingeahelad ja abiahelad pingestatakse nimipingega ±5 %,vooluahelad vooluta ja vooluklemmid ühendamata, impulsgeneraatori ja arvesti vahelise kaabli pikkus 1 m, sümmeetrilise sisestuse katse, nt liin-liin, faasinurk, impulsid tuleb rakendada 600 ja 2400 juures toitepinge nullläbivuspunktist, katsepinge vooluahelatele ja pingeahelatele, võrguliinid, 4 kV, generaatori impedants 2 Ω, katsepinge abiahelatele pingega üle 40 V kuini 1 kV, generaatori impedants 42 Ω, impulside arv 5 positiivset ja 5 negatiivset, kordamisaeg maksimaalselt 1/min